Welcome to Prosurge Lightning and Surge Protection manufacturer and solution provider!
Products

UL listed per UL1449 4th edition PV surge protective Device

Product Name: UL listed per UL1449 4th edition PV surge protective Device
Part Series: SPV series
Application: for PV/solar energy surge protection
Description: Prosurge type 1 UL1449 listed PV SPD with high SCCR

PROSURGE® SPV series fully comply with UL1449 4th editionas Type 1 SPD.


Nowadays, Photovoltaic systems (PV System) range from small,rooftop-mounted or building-integrated systems with capacities from a few to several tens of kilowatts, to large utility-scale power stations of hundreds of megawatts, and in the meanwhile the potential impact of lightning events increases with PV system size. Where lighting occurrences are frequent,unprotected PV systems can suffer repeated and significant damage to key components.This results in substantial repair and replacement costs, system downtime and the loss of revenue. Properly installed surge protective devices (SPDs) will minimize the potential impact of lightning events.

PROSURGE® SPV series employ high energy Metal Oxide Varistor (MOV), and constructed with our patented thermal protection and arc extinguishing technology which ensure safe disconnection while faulty current or abnormal voltage happened. These series are of single pole, Y connection and V connection for various applications in worldwide Photovoltaic systems, while the Y connection configuration is consisting of three protective paths for both Common mode & Differential mode protection,and the V connection configuration has two protective paths for Common mode protection.

Usually, sensitive electrical equipments of photovoltaic system like AC/DC Inverter, monitoring devices and PV array should be protected by PV surge protective devices (SPD). PROSURGE® SPV series are recommended for used on the dc-side of the DC-AC inverter, and PROSURGE® SP series on the ac-side to protect AC mains power supplies. The number and location of SPV SPDs on the DC side depend on the length of the cables between the PV array and inverter.The SPV SPD should be installed as close as possible to the inverter if the length is less than 10 meters. If it is greater than 10 meters, two SPDs are necessary,and one should be located in the box close to the PV array, another is located in the inverter area.

  

Ø  UL1449-4th Type 1 listed Surge Protective Devices for PV/ Photovoltaic system.

Ø  For single mode protection

Ø  UL1449-4th,Short circuit current rating (SCCR) up to100kA

Ø  Pluggable design with window fault indication

Ø  Surge capacity 50kA 8/20 per pole

Ø  Remote alarm signal optional 

Part No.

SPV48-V-S

SPV500-V-S

SPV600-V-S

In accordance with

UL1449-4th

Category IEC/VDE

Type1

Protection Mode

Single mode

Nominal voltage (Vdc)

Un

48

500

600

Max. permitted DC voltage

Vpvdc

85

560

670

Nominal discharge current(8/20)

In

20kA

Max. discharge current(8/20)

Imax

50kA

Voltage protection rating

VPR

<0.25kV

<1.5kV

<1.8kV

Leakage(Quiescent)  current

Iq

<20μA

<20μA

<20uA

Short Circuit Current Rating

SCCR

100kA

Response time

≤25 ns

Follow current

No

Max Ambient temperature

- 40ºC ~ + 85ºC

Cross-section of connection wire

Single-strand 35mm2; multi-strand 25mm2

Mounting

35mm DIN-rail in accordance with EN 50022/DIN46277-3

Enclosure material

thermoplastic; extinguishing degree UL94 V-0

Degree of protection

IP20

Installation width

1 module, DIN 43880

Thermal disconnector

Internal  green – normal ; red - failure

Remote alarm contact

“-S” means with remote alarm contact

Additional data for Remote Alarm Contacts

Remote alarm contact type

Isolated Form C

Switching capability Un/In

AC: 250V/0.5A     DC: 250V/0.1A; 125V/0.2A; 75V/0.5A

Max. Size of connecting wire

Max. 1.5mm2(or # 16AWG)

Replaceable Module Part No.

SP85D

SP560D

SP670D


Part No.

SPV48-V-C-S

SPV500-V-C-S

SPV600-V-C-S

In accordance with

UL1449-4th

Category IEC/VDE

Type1

Protection Mode

Common mode

Nominal voltage (Vdc)

Un

48

500

600

Max. permitted DC voltage

Vpvdc

85

560

670

Nominal discharge current(8/20)

In

20kA

Max. discharge current(8/20)

Imax

50kA

Voltage protection rating

VPR

<0.25kV

<1.5kV

<1.8kV

Leakage (Quiescent)  current

Iq

<20μA

<20μA

<20μA

Short Circuit Current Rating

SCCR

100kA

Response time

≤25 ns

Follow current

No

Max Ambient temperature

- 40ºC ~ + 85ºC

Cross-section of connection wire

Single-strand 35mm2; multi-strand 25mm2

Mounting

35mm DIN-rail in accordance with EN 50022/DIN46277-3

Enclosure material

thermoplastic; extinguishing degree UL94 V-0

Degree of protection

IP20

Installation width

2 modules, DIN 43880

Thermal disconnector

Internal  green – normal ; red - failure

Remote alarm contact

“-S” means with remote alarm contact

Additional data for Remote Alarm Contacts

Remote alarm contact type

Isolated Form C

Switching capability Un/In

AC: 250V/0.5A     DC: 250V/0.1A; 125V/0.2A; 75V/0.5A

Max. Size of connecting wire

Max. 1.5mm2(or # 16AWG)

Replaceable Module Part No.

SP85D

SP560D

SP670D


Part No.

SPV600-V-CD-S

SPV800-V-CD-S

SPV1000-V-CD-S

SPV1200-V-CD-S

SPV1500-V-CD-S

In accordance with

 UL1449-4th

Category IEC/VDE

Type1

Protection Mode

Common mode & Differential mode

Nominal voltage (Vdc)

Un

600

800

1000

1200

1500

Max. permitted DC voltage

Vpvdc

700

920

1120

1340

1650

Nominal discharge current(8/20)

In

20kA

Max. discharge current(8/20)

Imax

50kA

Voltage protection rating per mode

VPR

<1.0kV

<1.2kV

<1.5kV

<1.8kV

<2.2kV

Voltage protection rating (“+/-“ - PE)

<2kV

<2.4kV

<3.0kV

<3.6kV

<4.5kV

Leakage(Quiescent)  current

Iq

<20μA

<20μA

<20μA

<20μA

<20μA

Short Circuit Current Rating

SCCR

100kA

Response time

≤25 ns

Max Ambient temperature

- 40ºC ~ + 85ºC   

Cross-section of connection wire

Single-strand 35mm2; multi-strand 25mm2

Mounting

35mm DIN-rail in accordance with EN 50022/DIN46277-3

Enclosure material

thermoplastic; extinguishing degree UL94 V-0

Degree of protection

IP20

Installation width

3 modules, DIN 43880

Thermal disconnector

Internal  green – normal ; red - failure

Remote alarm contact

“-S” means with remote alarm contact

Additional data for Remote Alarm Contacts

Remote alarm contact type

Isolated Form C

Switching capability Un/In

AC: 250V/0.5A     DC: 250V/0.1A; 125V/0.2A; 75V/0.5A

Max. Size of connecting wire

Max. 1.5mm2(or # 16AWG)

Replaceable Model Part No.

SP350D

SP460D

SP560D

SP670D

SP825D


Part No.

SPV600-V-CD2-S

SPV800-V-CD2-S

SPV1000-V-CD2-S

SPV1200-V-CD2-S

SPV1500-V-CD2-S

In accordance with

UL1449-4th

Category IEC/VDE

Type1

Protection Mode

Common mode & Differential mode

Nominal voltage (Vdc)

Un

600

800

1000

1200

1500

Max. permitted DC voltage

Vpvdc

700

920

1120

1340

1650

Nominal discharge current(8/20)

In

20kA

Max. discharge current(8/20)

Imax

50kA

Voltage protection rating per mode

VPR

<1.0kV

<1.2kV

<1.5kV

<1.8kV

<2.2kV

Voltage protection rating (“+/-“ - PE)

<2kV

<2.4kV

<3.0kV

<3.6kV

<4.5kV

Leakage(Quiescent)  current

Iq

<20μA

<20μA

<20μA

<20μA

<20μA

Short Circuit Current Rating

SCCR

100kA

Response time

≤25 ns

Max Ambient temperature

- 40ºC ~ + 85ºC

Cross-section of connection wire

Single-strand 35mm2; multi-strand 25mm2

Mounting

35mm DIN-rail in accordance with EN 50022/DIN46277-3

Enclosure material

thermoplastic; extinguishing degree UL94 V-0

Degree of protection

IP20

Installation width

5 modules, DIN 43880

Thermal disconnector

Internal  green – normal ; red - failure

Remote alarm contact

“-S” means with remote alarm contact

Additional data for Remote Alarm Contacts

Remote alarm contact type

Isolated Form C

Switching capability Un/In

AC: 250V/0.5A     DC: 250V/0.1A; 125V/0.2A; 75V/0.5A

Max. Size of connecting wire

Max. 1.5mm2(or # 16AWG)

Replaceable Model Part No.

SP350D

SP460D

SP560D

SP670D

SP825D